Sprsun Heat Pump 19KW ERP A+++ R32 COLD CLIMATE EVI full Inverter Monoblock

4,290.00

Max. Heating Capacity (A7℃/W35℃): 19.8KW
Power Supply: 220V~240V/50Hz/1ph
Running Temp: -30℃~45℃
Max. Cooling Capacity(A35℃/W18℃): 18.1KW
Controller:  5-inch touch screen controller
Multi-functions: hot water/heating/cooling/hot water+cooling/hot water+heating
Model No. CGK050V3L-B

 

SKU: CGK050V3L-B Categories: , ,

This SPRSUN R32 DC Inverter Air to Water Heat Pump adopts the Panasonic rotary compressor and significantly improve the problem of insufficient heating efficiency at low temperature. It features a maximum heating capacity of 19.8KW/20KW and a maximum cooling capacity of 18.1KW/18.2KW. This air to water heat pump is perfect for properties in cold areas or cold climates as it uses the outdoor air as their heat source in the winter and heat sink in the summer. Hence, it’s cost-effective and environmental-friendly.

With a concise new look, the SPRSUN Self-developed Controller Series of SPRSUN R32 Cold Climate Full Inverter Sprsun Heat Pump 19KW are designed to bring comfort to people’s life with hot water, heating and cooling. The features & functions equivalent to the CAREL Controller Series include ERP A+++ energy rating, low noise operation, R32 refrigerant, smart control and intelligent defrosting. Moreover, these cost-effective inverter heat pumps are highlighted with 5-inch colorful touch screen, -30°C EVI low ambient temperature operation and one click remote software update.

Technical Specifications

Model CGK050V3L-B CGK-050V3L-B
Power Supply / Refrigerant V/Hz/Ph 220-240/50/1 – R32 380-420/50/3 – R32
Max. Heating Capacity (1) kW 19.8 20
C.O.P (1) W/W 4.71 4.72
Heating Capacity Min./Max.(1) kW 9.108 / 19.8 9.2 / 20
Heating Power Input Min./Max.(1) W 1547 / 4204 1559 / 4237
C.O.P Min./Max. (1) W/W 4.71 / 5.89 4.72 / 5.90
Max. Heating Capacity (2) kW 19.0 19.2
C.O.P (2) W/W 3.77 3.78
Heating Capacity Min./Max.(2) kW 8.74 / 19.01 8.83 / 19.20
Heating power input Min./Max.(2) W 1954 / 5045 1970 / 5085
C.O.P Min./Max. (2) W/W 3.77 / 4.47 3.78 / 4.48
Max. Cooling Capacity (3) kW 18.1 18.2
E.E.R (3) W/W 3.65 3.66
Cooling Capacity Min./Max.(3) kW 8.31 / 18.06 8.39 / 18.24
Cooling Power Input Min./Max.(3) W 1894 / 5774 1909 / 5820
E.E.R Min./Max. (3) W/W 3.13 / 4.39 3.13 / 4.39
Max. Cooling Capacity (4) kW 14.3 14.4
E.E.R (4) W/W 2.74 2.75
Cooling Capacity Min./Max.(4) kW 6.56 / 14.26 6.62 / 14.40
Cooling Power Input Min./Max.(4) W 1699 / 5353 1713 / 5405
E.E.R Min./Max. (4) W/W 2.66 / 3.86 2.66 / 3.87
Rated Current A 20.1 8.9
Max Power Input kW 6.1 6.1
Max Current A 29.17 12.97
Compressor Type – Quantity/System Twin Rotary – 1 Twin Rotary – 1
Fan Quantity 2 2
Airflow m3/h 5000 5000
Rated power W 200 210
Water Side Heat Exchanger Type Plate Heat Exchanger Plate Heat Exchanger
Water Pressure Drop kPa 23 25
Piping Connection Inch G1″ G1″
Allowable Water Flow Min./Rated./Max. L/S 0.59 0.95 1.58 0.66 1.05 1.75
Noise Level dB(A) 61 62
Net Dimension(L×D×H) mm 1110*475*1355 1110*475*1355
Packing Dimension(L×D×H) mm 1200*540*1510 1200*540*1510
Net Weight Kg 124 124
Gross Weight Kg 161 161
Note:  (1) Heating condition: water inlet/outlet temperature: 30℃/35℃, Ambient temperature: DB 7℃/WB 6℃;
         (2) Heating condition: water inlet/outlet temperature: 40℃/45℃, Ambient temperature: DB 7℃/WB 6℃;
         (3) Cooling condition: water inlet/outlet temperature: 23℃/18℃, Ambient temperature: DB35℃/WB24℃;
         (4) Cooling condition: water inlet/outlet temperature: 12℃/7℃, Ambient temperature: DB35℃/WB24℃.